4.0 W IRING
THE
M ETER
WIRING OVERVIEW
Electrical connections are made via screw-clamp terminals located on the
back of the meter. All conductors should conform to the meter ’s voltage and
current ratings. All cabling should conform to appropriate standards of good
installation, local codes and regulations. It is recommended that power supplied
to the meter (DC or AC) be protected by a fuse or circuit breaker.
When wiring the meter, compare the numbers embossed on the back of the
meter case against those shown in wiring drawings for proper wire position.
Strip the wire, leaving approximately 0.3" (7.5 mm) bare lead exposed (stranded
wires should be tinned with solder). Insert the lead under the correct screw-
clamp terminal and tighten until the wire is secure. (Pull wire to verify
tightness.) Each terminal can accept up to one #14 AWG (2.55 mm) wire, two
#18 AWG (1.02 mm), or four #20 AWG (0.61 mm).
EMC INSTALLATION GUIDELINES
Although this meter is designed with a high degree of immunity to Electro-
Magnetic Interference (EMI), proper installation and wiring methods must be
followed to ensure compatibility in each application. The type of the electrical
noise, its source or the method of coupling into the unit may be different for
various installations.Listed below are some EMC guidelines for successful
installation in an industrial environment.
1. The meter should be mounted in a metal enclosure, which is properly
connected to protective earth.
2. With use of the lower input ranges or signal sources with high source
impedance, the use of shielded cable may be necessary. This helps to guard
against stray AC pick-up. Attach the shield to the input common of the meter.
Line voltage monitoring and 5A CT applications do not usually require
shielding.
3. To minimize potential noise problems, power the meter from the same power
branch, or at least the same phase voltage as that of the signal source.
4.1 POWER WIRING
4. Never run Signal or Control cables in the same conduit or raceway with AC
power lines, conductors feeding motors, solenoids, SCR controls, and
heaters, etc. The cables should be run in metal conduit that is properly
grounded. This is especially useful in applications where cable runs are long
and portable two-way radios are used in close proximity or if the installation
is near a commercial radio transmitter.
5. Signal or Control cables within an enclosure should be routed as far away as
possible from contactors, control relays, transformers, and other noisy
components.
6. In extremely high EMI environments, the use of external EMI suppression
devices, such as ferrite suppression cores, is effective. Install them on Signal
and Control cables as close to the unit as possible. Loop the cable through the
core several times or use multiple cores on each cable for additional
protection. Install line filters on the power input cable to the unit to suppress
power line interference. Install them near the power entry point of the
enclosure. The following EMI suppression devices (or equivalent) are
recommended:
Ferrite Suppression Cores for signal and control cables:
Fair-Rite # 0443167251 (RLC #FCOR0000)
TDK # ZCAT3035-1330A
Steward #28B2029-0A0
Line Filters for input power cables:
Schaffner # FN610-1/07 (RLC #LFIL0000)
Schaffner # FN670-1.8/07
Corcom #1VR3
Note: Reference manufacturer ’s instructions when installing a line filter.
7. Long cable runs are more susceptible to EMI pickup than short cable runs.
Therefore, keep cable runs as short as possible.
8. Switching of inductive loads produces high EMI. Use of snubbers across
inductive loads suppresses EMI.
Snubber: RLC#SNUB0000.
AC Power
Terminal 1: VAC
DC Power
Terminal 1: +VDC
Terminal 2: VAC
1
2
Terminal 2: -VDC
1
2
+
-
4.2 INPUT SIGNAL WIRING
PAXD INPUT SIGNAL WIRING
Before connecting signal wires, the Input Range Jumper and Excitation Jumper should be verified for proper position.
Voltage Signal
(self powered)
Terminal 3: +VDC
Terminal 5: -VDC
Current Signal
(self powered)
Terminal 4: +ADC
Terminal 5: -ADC
Current Signal (2 wire
requiring excitation)
Terminal 4: -ADC
Terminal 6: +ADC
Excitation Jumper: 24 V
Current Signal (3 wire
requiring excitation)
Terminal 4: +ADC (signal)
Terminal 5: -ADC (common)
Terminal 6: +Volt supply
Excitation Jumper: 24 V
+Vs
3 4 5
+ -
300VDC MAX.
4
+
Load
2A DC MAX.
-
5
4 5
2 WIRE
- TRANSMITTER
6
+
+24V
Voltage Signal (3 wire
requiring excitation)
Terminal 3: +VDC (signal)
Terminal 5: -VDC (common)
Terminal 6: +Volt supply
Excitation Jumper: 24 V
3 4 5 6
Vout Iout COMM.
3 WIRE TRANSMITTER
11
相关PDF资料
PB-1583-TF BOX ABS 4.37X3.12X2" BK 1=10PCS
PB-1583 BOX ABS 4.37X3.12X2" BK 1=10PCS
PBS-11273 BOX ABS 6.30" X 3.75" X 1.41" BK
PBS-11275 BOX ABS 6.30" X 3.75" X 1.41" BK
PBS-11294-G BOX 5.62" X 3.25" X 1.5" GRAY
PBS-11327-B BOX 5.62" X 3.25" X 1.5" BLACK
PBS-11532-B BOX 4.37" X 3.25" X 1.52" BLACK
PBS-12631AV2G SWITCH PUSHBUTTON SPDT 6A 125V
相关代理商/技术参数
PAXTM110 制造商:Red Lion Controls 功能描述:TIMER, FIELD UPGRADEABLE GREEN DC 制造商:Red Lion Controls 功能描述:DC TIMER FIELD GREEN
PAXUSB00 制造商:Red Lion Controls 功能描述:USB PROGRAMMING CARD FOR PAX SERIES 制造商:Red Lion Controls 功能描述:USB OPTION CARD
PAY23015A12 功能描述:硬公制连接器 LOCKING PIN ASSEMBLY RoHS:否 制造商:TE Connectivity / AMP 系列:Z-Pack 产品类型:Receptacles 排数:5 位置/触点数量:110 安装角:Right 端接类型:Pin 外壳材料:Polyester 触点材料:Phosphor Bronze 触点电镀:Gold 类型:
PAY23015A1A1 功能描述:硬公制连接器 GRIP FINGER RoHS:否 制造商:TE Connectivity / AMP 系列:Z-Pack 产品类型:Receptacles 排数:5 位置/触点数量:110 安装角:Right 端接类型:Pin 外壳材料:Polyester 触点材料:Phosphor Bronze 触点电镀:Gold 类型:
PAY245A10 功能描述:手工工具 HM2 CONTACT EXTR TOOL-LONG PINS RoHS:否 制造商:Molex 产品:Extraction Tools 类型: 描述/功能:Extraction tool
PAY245A106 功能描述:手工工具 RoHS:否 制造商:Molex 产品:Extraction Tools 类型: 描述/功能:Extraction tool
PAY245A11 功能描述:手工工具 HM2 CONTACT EXTR TOOL-SHORT PINS RoHS:否 制造商:Molex 产品:Extraction Tools 类型: 描述/功能:Extraction tool
PAY245A112 功能描述:手工工具 INSERT BLOCK RoHS:否 制造商:Molex 产品:Extraction Tools 类型: 描述/功能:Extraction tool